Self-regulating heating cable CAHT CGf – 50w/m – 230 V – 50m

750,00

This CABT heating cable 50 w/m is a high qualitity self-regulating heating cable with length of 50m. It consists of a plastic semi-conductor heating element which adapts its heat output according to the local temperature of the self-regulating heating cable.

Self-regulating heating cable with tinned copper braid and polyolefin over jacket
CABT heating cables withstand 65°C power on / 75°C power off
Power output : 50 w/m

Description

CAHT high temperature self-regulating heating cable consist of a heating semiconductor
plastic element which adapts its calorific power (W/m) on each point depending on the
local temperature. This intrinsic feature of the semiconductor heating element allows
in some cases to dispense of using a thermostatic controler (self-regulation).
They can be cut on the adjusted length directly on the job site.
For your heat tracing installations and especially on temperature maintenance of hot water
systems, we strongly recommend the combination of our electronic THS / E controllers with
a Pt1000 sensor to apply directly on the pipe.
The latter are equipped with a current absorber for start up of self regulating
heating cables. They are the guarantee of a rigorous and reliable electronics regulation
(energy saving of + 50%).
The fluoropolymer insulation is the gaurantee of a perfect thermal and chemical resistance.

Advantages

– can be cut directly on the adjusted length on the site.
– allow derivation from a unique and single feed point.
– semiconductor heating element adapts its power locally.
– good flexibility allowing the tracing of hydraulic organs (valves, pumps, …)
– allow overlaps during implementation (self-regulating).
– maxi exposure temp energized : 120° C (power ON) / de-energized (power OFF) : 200°C.
– construction in accordance with the European standards in force

Main features

– FEP fluoropolymer jacket
– FEP fluoropolymer overjacket (CGf version) for corrosive and chemically aggressive environments.
– voltage: 230 V / 240 V / 50 or 60 Hz (115 V optional).
– thermal calibration: Max. rated current * 2.
– use C or D curve circuit breakers.
– possibility of a maximum current spike of 3 * In / 300ms.
– necessary use differential circuit breaker: 30 mA.
– maximum length / power point = approximately 110 m.
– maxi temperature exposure : power ON = 120°C
– maxi temperature exposure : power OFF = 200°C
– maxi temperature maintenance advised : 85°C

 

 